Suspensions for pipes are used for free horizontal placement of pipes of automatic extinguishing units and provide secure fixation of the pipeline on set height. Used in all types of buildings: living, social manufacturing and storage.
|
Suspension for pipes
|

Size reference
|
- Made from sheet steel 08PS-5 RNS 14918 with following hot zincification.
- Height of pipe placement in extinguishing system is controlled by a threaded stud.
- Suspensions for pipes of SP D” are offered, where D”– is a nominal size of a pipe gap in inches, for which given suspension is aimed.
|
Standard sizes and technical rates of suspensions for water extinguishing pipes
|
Symbolic notation
|
Nominal size, mmD
|
Sizes, mm
|
Weight, kg/ 100 ea.
|
Max capacity, кN
|
|
C1
|
C2
|
|
SP 1"
|
25
|
63
|
23
|
6.2
|
1.3
|
|
SP 11/4"
|
32
|
78
|
26
|
7.8
|
1.3
|
|
SP 11/2"
|
40
|
90
|
35
|
9.2
|
1.3
|
|
SP 2"
|
50
|
93
|
26
|
10.2
|
1.3
|
|
SP 21/2"
|
65
|
125
|
42
|
12.2
|
2.2
|
|
SP 3"
|
80
|
136
|
41
|
13.3
|
2.2
|
|
SP 4"
|
100
|
179
|
55
|
16.4
|
2.2
|
|
SP 6"
|
150
|
235
|
102
|
22.1
|
2.2
|
|