Diagram of irrigation intensity dependence on pressure at application of water and water solutions with capacity factor K=0.3 on 12 m2 protected area
Diagram of irrigation intensity dependence on pressure at application of foam solutions with capacity factor K = 0.3 on 12 m2 protected area
Diagram of irrigation intensity dependence on pressure at application of water and water solutions with capacity factor K=0.3 on 12 m2 (two or more)
Installation height 2,5m for upright water-mist sprinklers
Sprinkler map of irrigation intensity for upright sprinklers at application of water and water solutions with capacity factor K=0,3/80/5,6
(0,1; 0.2; 0,3 and 0,4 MPa)
Installation height – 2.5 m.
Sprinkler map of irrigation intensity for upright sprinklers at application of foam solutions with capacity factor K=0,3/80/5,6
(0,15; 0.2; 0,3 and 0,4 MPa)
Installation height – 2.5 m.
Atomizer weight | 0,074 |
Connecting thread | ½ |
Dimensions | 58х30 |
Installation orientation | Pendent |
K-factor | 4,0 (57) |
Outlet diameter | 9,4 |
Performance factor | 0,3 |
Protected area | 12 m2 |
Sprinkler flask diameter | 3 mm |
Sprinkler response temperature | 57° С, 68° С , 93°С |