Maximum Differential Addressable Satellite Point HFD. The detector is mounted on the ceiling or a bracket and is located in the vicinity of EAS, provides a forced start of the sprinkler.
Fire detectors are addressable devices from Olimp I.
Connected to the CL-I, has in its composition the control device of EAS. This device contains a block of ionic cells (supercapacitors), the stored energy of which is used for forced electric start (heating) EAS on command from BKU-I. Satellite detectors provide control of the ionistors' charge and their recharge from the SLI. Connected EASs are automatically controlled for serviceability of communication line with them (breakage, short circuit) and for opening (activation of EAS).
Time of technical readiness of satellite power supply after full discharge of ionic batteries is not more than 45 minutes. Time of technical readiness of SLI with 250-satellite power supply and/or ISS-I after full discharge of ionizers - no more than 48 hours.
Features
: - satellite HFD;
- control and monitoring of EAS;
- activation of EAS on command from the BKU-I;
- up to 15 dependent satellite FD and MKS-I (addresses programmable);
- programmable temperature threshold (54-1000C, step 10C).
Technical Specifications:
Parameter |
Maximum value |
Voltage in the SLI | 18 - 24 V |
Current consumption from the SLI, not more: in "Ionizer charge " mode in all other modes |
17,2 mА 0,2 mА |
Enclosure degree of protection |
IP41 |
Overall dimensions, not more than |
92 мм, Ø 110 мм |
Weight, not more than |
0,25 kg |
Dimensions, mm | 92 мм, Ø 110 мм |
Power supply: current, no more | 0,15 mА |
Sheath protection degree | IP41 |
Temperature regime | from –20 to +80 °С |
Weight | 0,2 kg |